不同类别的冷凝器安装在不同位置的好处

人气:136 评论:0 日期:2018-05-15 10:49:28

现在冷库是很多领域中都需要配置的,而要冷库,就需要使用到制冷辅机。各种型式的冷凝器都应按冷库工艺流程,与油分离器、贮液器就近布置。冷凝器的安装高度,必须保证其液体按自流条件流入贮液器内。今天来说说冷凝器的安装位置可以随意吗。
Nowadays, cold storage is needed in many fields, and cold storage is necessary for refrigeration auxiliaries. All types of condensers should be arranged in close proximity to the oil separator and liquid receiver according to the cold storage process. The installation height of the condenser must ensure that the liquid flows into the reservoir according to the self flow condition. Today, let's talk about the installation position of the condenser.

1、卧式冷凝器

卧式冷凝器须设置在冷库设备间内,不得设在露天。为节省占地买年纪,与贮液器上下分层布置。在冷凝器一端要留有清洗、更换管子的空间(约为冷凝器长度的1.5倍)。在冷凝器两端的上方要留有吊起端盖的空间。台数多时,可设操作平台。为保证冷凝器出液顺畅,其出液口应高于其出液管截止至少300mm。

1. The horizontal condenser:

Horizontal condenser must be installed in the cold storage equipment room, not in the open air. In order to save the land and buy the age, the upper and lower layers of the liquid storage device are arranged. At the end of the condenser, there is room for cleaning and replacing pipes (about 1.5 times the length of the condenser). At the top of both ends of the condenser, there is room for lifting the end cover. The operating platform can be set up for many times. In order to ensure that the condenser outlet is smooth, its outlet should be higher than its outlet pipe at least 300mm.

2、淋浇式冷凝器:

淋浇式冷凝器需布置在机房外开敞、通风处或机房屋顶上。其排管正面应垂直于该地区夏季的主导风向。在风大的地区,冷凝器四周应设百页挡水板。

2. Drenching type condenser:

The sprinkling condenser should be arranged in the open, ventilated place or the roof of the engine room outside the engine room. The front of the pipe should be perpendicular to the dominant wind direction in summer. In the windy area, there should be 100 pages of water baffle around the condenser.

3、立式冷凝器:

立式冷凝器应布置在机房外,且应尽量避免太阳直接照射。冷凝器的水池壁与设备间墙面应有3m间距,以减小冷却水外溅对墙面的损坏。立式冷凝器通常利用底部水池作为基础。冷凝器上方要留有清洗和更换管子的空间。为了便于操作,应设有钢结构的操作平台。

3. Vertical condenser:

Vertical condenser should be placed outside the engine room, and direct solar radiation should be avoided as far as possible. The 3M between the tank wall of the condenser and the wall of the equipment should be reduced to reduce the damage caused by splashing of cooling water on the wall. Vertical condensers usually use the bottom tank as the foundation. The space above the condenser should be cleaned and replaced. In order to facilitate operation, there should be a steel structure operation platform.